Sungrow’s PowerTitan 3.0 battery energy storage system underwent a large-scale fire test involving 28.56 MWh of battery storage and a 7.4 MW medium-voltage substation. According to the company, thermal runaway remained confined to the initiating container.
UL Solutions conducted the test, witnessed by Fire Risk Alliance and observed by Jensen Hughes. Sungrow said testing followed the applicable requirements of UL 9540A: 2026 and CSA/ANSI C800-2025.
The configuration replicated a utility-scale installation. PowerTitan 3.0 combines liquid-cooled stacked battery cells and a DC/AC power converter within a single 6-m (20-foot) container.
The batteries were at 100 % state of charge, with the initiating and neighbouring containers positioned closely back-to-back. Active fire suppression and thermal management systems were disabled, while the initiating container’s rooftop pressure-relief panels were fully opened to maximise ventilation.
Monitoring continued for 7.5 hours. The peak internal temperature in the initiating container reached 1,259.8°C. Sungrow reported that cell temperatures in adjacent containers remained below the thermal runaway threshold specified under UL 9540A: 2026, with no propagation to those containers or the substation.
The company said the initiating container remained structurally intact and could be lifted as a complete unit after testing. Four adjacent containers also retained their structural integrity without deformation.
Before the physical test, Sungrow conducted simulation-based assessments across hundreds of scenarios and operating conditions. The company said simulated fire intensity and development trends closely matched the observed results.
Source: Energy Global